IGS-NT Communication Guide
35
3.2.5 Ethernet connection (Direct)
Controllers
Controllers IG-NT-BB IG-NTC IS-NTC-BB IM-NTC-BB IM-NT-BB
Connection
applicable
NO YES YES YES NO
Available
ports
external bridge ETHERNET ETHERNET ETHERNET external bridge
More info IG/IS/IM-NTC-BB - Communications (page 12)
Controllers IG-NT IG-NTC IS-NT-BB IM-NT
Connection
applicable
NO NO NO NO
Available
ports
external bridge external bridge external bridge external bridge
Note: Ethernet connection is available for all mentioned controllers via external internet bridge or IB-NT (see
Ethernet connection via IB-NT on page 34).
Number of clients connected simultaneously
2 clients with InteliMonitor or Web Server (Comap/TCP protocol)
2 clients with web interface
Ethernet connection settings
Perform the connection settings the same way as for Ethernet connection (Direct) (page 27).
Note: The IP addresses of the controllers must be accessible from the remote computer. If the remote
computer is connected into another LAN segment than the gen-sets are, there must be a gateway(s) that enable
direct traffic between the segments. If the remote computer is connected via Internet, then the internet gateway
of the LAN where gen-sets are connected must have public IP address, must allow incoming traffic and must
provide port forwarding from the external public IP to the different internal gen-set IPs according to the port
used.