EMS-96 Instruction Manual IM1200-U v1.6 Pag. 39 / 48
Setup Setpoint
Setpoint XX (from 1 to 32)
Enable or disable the setpoint function.
Internal measures / Measures node X
Select the instrument from which the measure to analyze it will be read.
Selection of the group for the actual setpoint if it is set Internal measures as Source.
See acronym in the table of the group selected
Selection of the measure in the selected Measure Group of the actual setpoint.
The Action is executed if the measure exceed the set value.
With Measure node X as Source, the multiplier factor will be 1, 1000, 1000000 while with Internal measures there will be:
Voltage: mV-V-kV-MV Reactive power: VAr-kVAr-MVAr–GVAr Angle: degree*10
Current: mA-A-kA-MA Frequency: mHz Apparent energy: VAh*100-kVAh-MVAh-GVAh
Apparent power:VA-kVA-MVA-GVA Temperature: °C Active energy: Wh*100-kWh-MWh-GWh
Active power: W-kW-MW-GW THD and harmonics: %*100 Reactive energy: VArh*100-kVArh-MVArh-GVArh
The Action is executed if the measure is lower than the set value.
See the description of High threshold unit.
0: instantaneous execution of the Action
1÷10000: execution of the Action if the condition is kept for the time set
0: instantaneous execution of the Action
1÷10000: execution of the Action if the condition is kept for the time set
Hysteresis (for high & low threshold)
Setting a value different by 0, the hysteresis is enabled with a percentage value set.
- No logic: the Action is executed without to verify the status of others setpoint [Default].
- OR logic: the Action is execute after the check of result of the OR logic operation with the setpoint selected in operands.
- AND logic: the Action is execute after the check of result of the AND logic operation with the setpoint selected in operands.
WARNING: it’s not possible to set OR logic for logic operation over and logic operation entry at the same time.
- No logic: the Action is executed without to verify the status of others setpoint [Default].
- OR logic: the Action is execute after the check of result of the OR logic operation with the setpoint selected in operands.
- AND logic: the Action is execute after the check of result of the AND logic operation with the setpoint selected in operands.
WARNING: it’s not possible to set OR logic for logic operation over and logic operation entry at the same time.
Setpoint 1: select Yes to include the setpoint 01 in the logic.
- - - - - - - - - - - - - - - - - - -
Setpoint 16: select Yes to include the setpoint 16 in the logic.
Setpoint 17: select Yes to include the setpoint 17 in the logic.
- - - - - - - - - - - - - - - - - - -
Setpoint 32: select Yes to include the setpoint 32 in the logic.
It possible to select one, more or anything action:
- Display and save the event. - Increase a variable that indicates the number of events.
- Change the DO-X state. - Increase a variable that indicates the duration time of the event.
It possible to select one, more or anything action:
- Display and save the event. - Change the DO-X state
It possible to select (with Yes) one or more DO: DO-1, DO-2, DO-3, DO-4, DO-5, DO-6, DO-7, DO-8.
WARNING: for a correct functioning before to select the output it’s necessary to set the SETPOINT mode under the item MODE in
the setup page of the DO group (DO-1, 2, 3, 4 or DO-5, 6, 7, 8).