EMS-96 Instruction Manual IM1200-U v1.6 Pag. 40 / 48
Example of setting (in the correct order) to set an alarm when the voltage exceed 230V on the phases 1, 2 and 3 (V1 AND V2 AND V3) with
saving the event and the switching of a digital output when the alarm is present and when it disappear.
SETPOINT 1 (primary)
Source: Internal measures
Group: instant
Item: V1
High threshold: 230
High threshold unit: V
Over debounce: 10 (sec.)
Logic operation over: AND
Operands 1-16:
- Setpoint 2: yes
- Setpoint 3: yes
Action over:
- save event: yes
- DO change: yes
Action entry:
- save event: yes
- DO change: yes
DO used:
- DO-1: yes
Enable: yes
SETPOINT 2 (secondary)
Source: Internal measures
Group: instant
Item: V2
High threshold: 230
High threshold unit: V
Over debounce: 10 (sec.)
Enable: yes
SETPOINT 3 (secondary)
Source: Internal measures
Group: instant
Item: V3
High threshold: 230
High threshold unit: V
Over debounce: 10 (sec.)
Enable: yes