EMS-96 Instruction Manual IM1200-U v1.6 Pag. 43 / 48
Trigger
The measures you select will be sampled at intervals from 1 to 3600 seconds, but only after the occurrence of a specific event,
detected by the instrument.
The events can be set are of two types:
- digital input change state;
- Setpoint "exceeded limits".
Setup Log Trigger
Trigger Log (option)
Range
Default
Enable
yes / no
no
Enable or disable the trigger log. Before to enable the log functionality, it’s necessary to disable any other activated log.
It is possible to use only one type of log at a time.
Sampling [seconds]
1 ÷ 3600
10
Acquisition timing.
Storage Type
FIFO / end memory
end memory
Type of storage. Note: FIFO after 10 consecutive cycles is automatically disabled.
Trigger input
DI active high, DI active low, Setpoint
DI active high
Input that active the log.
DI used
1 ÷ 4
1
Digital input used for the trigger.
Setpoint used
1 ÷ 32
1
Setpoint used for the trigger.
Group 1
See Acronym Group table
---
Selection of the group for the 1
st
measure sampled for the trigger log.
Measure 1
See acronym in the table of the group selected
---
Selection of the 1
st
measure sampled for the trigger log.
………………..
………………..
Group 15
See Acronym Group table
---
Selection of the group for the 15
st
measure sampled for the trigger log.
Measure 15
See acronym in the table of the group selected
---
Selection of the 15
st
measure sampled for the trigger log.
Warning: All recordings for all log will be lost if any parameter is changed.
Example: Setup Log Trigger Sampling [s] 5
Storage type end memory
Trigger input setpoint
Setpoint used 1
Group 1 instant
Measure 1 W1
Enable yes
To display how many log were acquired and the remaining storing time:
Info Log summary Trigger.
To display the single log: