EasyManuals Logo

Control Techniques M'Ax 403 User Manual

Control Techniques M'Ax 403
116 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #102 background imageLoading...
Page #102 background image
*
96 M’Ax User Guide
Issue Number: 4
D.5 Gain sequencing
The Drive has three sets of PID gains and the SLM has a corresponding
set of PID buffers. Each PID-gains set in the Drive can be set up for a
different operating condition (e.g. a particular load and/or position). A
PID buffer in the
SLM can be activated within 1ms of a command being
received.
For example, lower values of PID gains can be used when a resonance
is traversed during acceleration, and the required values for the process
used when the range of operating speeds is reached.
The PID-gains parameters in Menu 0 relate to the parameters in PID
gains 1 (see Figure D-3). Selection among the three sets is made by
3.16 {0.12} Speed-loop gains selector.
Setting up PID gains for gain sequencing
Each PID-gains set is set up individually by following the procedure in
Adjusting the speed-loop gains or Specifying shaft stiffness and load
inertia. To ensure the required PID-gains set is adjusted while following
the procedure, set
3.16 {0.12} Speed-loop gains selector as follows:
Unlock security before adjusting these gains.
The parameters in each PID-gains set are as follows:
PID-gains set 1
3.10 {0.13} Speed-loop proportional gain Kp1
3.11 {0.14} Speed-loop integral gain Ki1
3.12 {0.15} Speed-loop derivative gain Kd1
4.12 {0.16} Current-demand filter 1 cut-off frequency
4.07 {0.18} Symmetrical current limit Kc1
PID-gains set 2
3.13 Speed-loop proportional gain Kp2
3.14 Speed-loop integral gain Ki2
3.15 Speed-loop derivative gain Kd2
4.23 Current-demand filter 2 cut-off frequency
4.24 Symmetrical current limit Kc2
PID-gains set 3
3.60 Speed-loop proportional gain Kp3
3.61 Speed-loop integral gain Ki3
3.62 Speed-loop derivative gain Kd3
4.27 Current-demand filter 3 cut-off frequency
4.28 Symmetrical current limit Kc3
Selection of PID-gains sets and PID buffers
Following power-up, new PID-gain(s) value(s) take
effect only after the motor shaft has passed through the
zero position of the feedback encoder.
When the motor is running or stopped, a PID buffer in the SLM (and the
related PID-gains set in the Drive) can be selected by any of the
following means:
Using the keypad or serial communications to adjust the PID-gains
selector
1. Change the setting of 3.16 {0.12} Speed-loop gains selector as
follows:
2. Set
11.63 SLM buffer update at 1.
3. The newly selected PID buffer takes effect immediately.
Using the keypad or serial communications to select by edge-
triggering
1. Set 3.16 {0.12} Speed-loop gains selector at 0. This allows PID
buffers to be selected by edge-triggering.
2. Refer to the following table and ensure the appropriate parameter is
first set at
0, then set it at 1 in order to select the required PID buffer;
the PID buffer is selected on the rising edge.
3. The newly selected PID buffer takes effect immediately.
Parameter Range(
ô
)Default(
ð
)Type
3.10 {0.13} Speed-loop proportional gain Kp1 0.0000 ~ 0.3000 0.0100 RW Uni
3.11 {0.14} Speed-loop integral gain Ki1 0.000 ~ 20.000 6.000 RW Uni
3.12 {0.15} Speed-loop derivative gain Kd1 0.0000 ~ 0.1000 0.0000 RW Uni
3.13 Speed-loop proportional gain Kp2 0.0000 ~ 0.3000 0.0100 RW Uni
3.14 Speed-loop integral gain Ki2 0.000 ~ 20.000 6.000 RW Uni
3.15 Speed-loop differential-feedback gain Kd2 0.0000 ~ 0.1000 0.0000 RW Uni
3.16 {0.12} Speed-loop PID gains selector 0 ~ 3 1 RW Uni
3.18 {0.11} Total inertia
0.01 ~ 600.00kgcm
2
RO Uni
3.19 {0.09} Stiffness angle 0 ~ 30.0° 6.0 RW Uni
3.20 {0.10} Load inertia
0.01 ~ 600.00kgcm
2
J
ML
RW Uni
3.57 Speed-loop buffer 1 select 0~1 0 RW Bit
3.58 Speed-loop buffer 2 select 0~1 0 RW Bit
3.59 Speed-loop buffer 3 select 0~1 0 RW Bit
3.60 Speed-loop proportional gain Kp3 0.0000 ~ 0.3000 0.0100 RW Uni
3.61 Speed-loop integral gain Ki3 0.000 ~ 20.000 6.000 RW Uni
3.62 Speed-loop derivative gain Kd3 0.0000 ~ 0.1000 0.0000 RW Uni
3.63 Speed-loop PID buffer in use indicator 0~3
RO Uni
3.16 PID gains
11
22
33
3.16 Select PID buffer...
11
22
33
To select
PID buffer...
Use parameter...
13.57
23.58
33.59
CAUTION

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Control Techniques M'Ax 403 and is the answer not in the manual?

Control Techniques M'Ax 403 Specifications

General IconGeneral
BrandControl Techniques
ModelM'Ax 403
CategoryServo Drives
LanguageEnglish

Related product manuals