MOBILTEX® DATA LTD.
TITLE:
RMU5 Generic Installation and Configuration Guide
Calgary, Alberta
DOCUMENT NO.:
RMU5-MAN-001
SHEET:
22 of 69
REV:
1.10
Source Voltage
Maximum Load Current
240V AC
100A
480V AC
80A
600V AC
70A
48V DC
100A
125V DC
50A
250V DC
30A
Table 2 Mercury Displacement Relay Contact De-rating
Figure 16 K07111NC12D 100A Mercury Displacement Relay
4.2.6 Door Switch Wiring
The RMU5 may be used to monitor the state of an installer-provided door switch contact. The contacts are debounced
for a programmable period. Any mechanical contact switch may be used. The door switch is wired as shown in Figure
17. Ensure that the wire jumper from the 12V terminal to the D-IN A terminal is not omitted.
Door Switch Wiring
Mechanical Switch Contacts
Figure 17 Door Switch Wiring
The digital input may also be used to monitor other types of contacts and for other purposes. The digital input may be
used to sense breaker trips for breakers that provide isolated trip detection contacts.
For active digital sensors, such as hall effect sensors, a 3 to 32VDC source attached between D-INA and D-INB will
result in an active input for sensing an enabled voltage source. If a voltage source is used, the 12V source from the
RMU5 is not connected to D-INA.