98
Table 6-8 Reactive Power Control (IEEE-1547 and Rule21, and ISO-NE)
Grid Reactive Power Derating
Setting Range
Parameter
Name
Description
IEEE1547-2018
Rule21
ISO-NE
Min
Default
Max
Min
Default
Max
Min
Default
Max
CtrMode
The control mode of
reactive power
0: Disable dispatch
mode
1: Remote dispatch
mode
2: Local control, by Q
3: Local control, by PF
4: PF(P) curve
5: Q(U) curve
6:Q(P)curve
0
3
6
0
5
6
0
0
2
Percentage
(%)
Local Power Factor
Setting
-60
0
60
-60
0
60
-60
0
100
PFSetValue
Local Power Factor
Setting
-1.0,
-0.8
1.0
0.8,
1.0
-1.0,
-0.8
-0.95
0.8,
1.0
-1.0,
-0.8
1.0
300
ReactivePow
erOver
Reactive power over-
provisioning enable
setting
0: Disable
1: Enable
0
0
1
0
0
1
0
0
300
PFCurveP1
%
Power of PF(P) Curve
point 1
0
50
110
0
50
110
0
50
110
PFpCurvePF
1
PF of PF(P) Curve
point 1
-1.0,
- 0.8
1.0
0.8,
1.0
-1.0,
- 0.8
1.0
0.8,
1.0
-1.0,
- 0.8
1.0
0.8,
1.0
PFCurveP2
%
Power of PF(P) Curve
point 2
0
100
110
0
100
110
0
100
110
PFpCurvePF
2
PF of PF(P) Curve
point 2
-1.0,
- 0.8
-0.9
0.8,
1.0
-1.0,
- 0.8
-0.9
0.8,
1.0
-1.0,
- 0.8
-0.9
0.8,
1.0
PFCurveTriV
ol (%)
The trigger voltage of
PF(P)Curve
100
100
110
100
100
110
100
100
110
PFCurveUnd
oVol (%)
PF curve revocation
voltage
90
90
100
90
90
100
90
90
100