Curtiss-Wright | Tritex II AC 90, 115 Rev. X PN39892 7/12/22
72
Internal RS 485 circuit
Connecting Multiple Tritex Actuators to a Modbus Master Host
Important considerations
Always use 3 conductors, RS485 +, RS485 and Reference.
A twisted pair for 485+ and 485- is preferred.
RS485 is a “multi-drop” network as opposed to a “star”, therefore
keep the drop (stub) to each actuator as short as possible. When
using the 8 mm connector use a T connector, such as the Exlar
PN TT458SP.
A termination resistor is not usually required.
RS485 +
RS485 -
RS485 REF
ADM3072E
+5v isolated
20
20
10kΩ
5 v isolated return
High speed
isolation
Receive Data
Transmit Data
Receive/Transmit
100Ω
PE
Shield