66
5. Network Service
Intelligent PDU Web Interface
SNMPv1 Page
Item Definition
Community
The name used to access the SNMP community from
a Network
Management System (NMS). Its maximum length is 15 characters.
IP Address
(IPv6 Support)
The IP address or IP address mask can be accessed by the NMS. A
specific IP address allows access only by the NMS with the specified
IP Address. The 255is regarded as the subnet mask and the rules
are as follows:
*192.168.20.255: Access only by an NMS on the 192.168.20.0
segment.
*192.255.255.255: Access only by an NMS on the 192.0.0.0 segment.
*0.0.0.0 (the default setting) or 255.255.255.255: Access by any
NMS on any segments.
Access Type
The allowable action for the NMS through the community and IP
address.
*Read Only: GET at any time but cannot SET.
*Write/Read: GET at any time. SET at any time unless someone logs
in to the Web interface.
*Forbidden: No GET or SET.