21
2. Advanced Power Management
Intelligent PDU Web Interface
2.4 Power Protection
The configurable load threshold can be set to prevent an overload condition. Coldstart
and system configurations are also offered for different user needs. See PDU Tab >
Device Manager.
PDU Tab > Manager > Device
Item Definition
HOST/GUEST#
Select the role of PDU (HOST or GUEST#) if PDUs are daisy
chained. Up to 3 GUEST PDUs can connect to 1 HOST PDU.
Load Configuration
Overload Threshold
Set the value for the total current on the PDU that will
signal an overload warning. Must be higher than Near
Overload Threshold and equal to or lower than the PDU
Rating in the
.
Near Overload
Threshold
Set the value for the total current on the PDU that will
signal a near overload warning. Must be between Overload
Threshold and Low Load Threshold.