Breadcrumb Field code Setting name Range, step
Default valu
e
Date Value
Field settings table
Installer setting at variance with
default value
9.A.2 [D-09] R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000
p
ulse/kWh
└─ Sensors
9.B.1 [C-08] R/W
0: No
1: Outdoor sensor
2: Room sensor
9.B.2 [2-0B] R/W -5~5°C, step: 0,5°C
0°C
9.B.3 [1-0A] R/W
0: No averaging
1: 12 hours
2: 24 hours
3: 48 hours
4: 72 hours
└─ Bivalent
9.C.1 [C-02] R/W
0: No
1: Bivalent
9.C.2 [7-05] R/W
0: Very high
1: High
2: Medium
3: Low
4: Ver
y
low
9.C.3 [C-03] R/W -25~25°C, step: 1°C
0°C
9.C.4 [C-04] R/W 2~10°C, step 1°C
3°C
Installer settings
9.D [C-09] R/W
0: Normally open
1: Normall
y
closed
9.E [3-00] R/W 0: No
1: Yes
9.F [E-08] R/W 0: Disabled
1: Enabled
9.G R/W 0: No
1: Yes
└─ Overview field settings
9.I [0-00] R/W [9-05]~min(45,[9-06])°C, step: 1°C
35°C
9.I [0-01] R/W [9-05]~[9-06]°C, step: 1°C
50°C
9.I [0-02] R/W 10~25°C, step: 1°C
15°C
9.I [0-03] R/W -40~5°C, step: 1°C
-10°C
9.I [0-04]
8
9.I [0-05]
12
9.I [0-06]
35
9.I [0-07]
20
9.I [0-0B] R/W 35~[6-0E]°C, step: 1°C
55°C
9.I [0-0C] R/W 45~[6-0E]°C, step: 1°C
60°C
9.I [0-0D] R/W 10~25°C, step: 1°C
15°C
9.I [0-0E] R/W -40~5°C, step: 1°C
-10°C
9.I [1-00] R/W -40~5°C, step: 1°C
-10°C
9.I [1-01] R/W 10~25°C, step: 1°C
15°C
9.I [1-02] R/W
[9-01]~[9-00], step: 1°C
35°C
9.I [1-03] R/W [9-01]~min(45, [9-00])°C , step: 1°C
25°C
9.I [1-04]
1
9.I [1-05]
1
9.I [1-06]
20
9.I [1-07]
35
9.I [1-08]
22
9.I [1-09]
18
9.I [1-0A] R/W
0: No averaging
1: 12 hours
2: 24 hours
3: 48 hours
4: 72 hours
9.I [1-0B] R/W 3~10°C, step: 1°C
5°C
9.I [1-0C] R/W 3~10°C, step: 1°C
5°C
9.I [1-0D]
5
9.I [1-0E]
5
9.I [2-00] R/W 0: Each day
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
7: Sunda
y
9.I [2-01] R/W 0: No
1: Yes
9.I [2-02] R/W 0~23 hour, step: 1 hour
1
9.I [2-03] R/W
60°C
What is the desired delta T in heating for the additional zone?
Electricity meter 2
External sensor
Leaving water value for high ambient temp. for DHW WD curve.
Averaging time
Bivalent
Boiler efficiency
Temperature
Hysteresis
Alarm output
Auto restart
Power saving function
Disable protections
Leaving water value for high ambient temp. for LWT add zone heating WD curve.
Leaving water value for high ambient temp. for LWT main zone heating WD curve.
What is the averaging time for the outdoor temp?
Leaving water value for low ambient temp. for LWT add zone heating WD curve.
High ambient temp. for LWT add zone heating WD curve.
Low ambient temp. for LWT add zone heating WD curve.
--
--
Leaving water value for low ambient temp. for LWT main zone heating WD curve.
Low ambient temp. for LWT main zone heating WD curve.
Should the disinfection function be executed?
When should the disinfection function start?
When should the disinfection function be executed?
--
What is the desired delta T in heating for the main zone?
--
--
--
--
What is the disinfection target temperature?
Low ambient temp. for DHW WD curve.
--
--
--
High ambient temp. for DHW WD curve.
High ambient temp. for LWT main zone heating WD curve.
--
Leaving water value for low ambient temp. for DHW WD curve.
--
Ext. amb. sensor offset
4P618955-1 - 2020.09 (#) Setting is not applicable for this unit.