Breadcrumb Field code Setting name Range, step
Default value
Date Value
Installer setting at variance with
default value
Field settings table
9.I [4-01] R/W
0: None
1: BSH
2: BUH
9.I [4-02] R/W 14~35°C, step: 1°C
22°C
9.I [4-03] R/W 0: Restricted
1: Allowed
2: Overlap
3: Compressor off
4: Le
g
ionella onl
y
9.I [4-04]
0: Intermittent
1: Continuous
2: Of
f
9.I [4-05]
0
9.I [4-06] R/W 0: Manual
1: Automatic(normal SH/DHW ON)
2: Auto red SH/DHW ON
3: Auto red SH/DHW OFF
4: SH ON/DHW OFF
9.I [4-07]
6
9.I [4-08] R/W
0: No limitation
1: Continuous
2: Di
g
ital in
p
uts
9.I [4-09] R/W 0: Current
1: Power
9.I [4-0A] R/W
0: 1 (*1)
1: 1/1+2 (*2) (*3)
2: 1/2
3: 1/2 + 1/1+2 in emer
g
enc
y
9.I [4-0B] R/W 1~10°C, step: 0,5°C
1°C
9.I [4-0D] R/W 1~10°C, step: 0,5°C
3°C
9.I [4-0E]
6
9.I [5-00] R/W 0: No
1: Yes
9.I [5-01] R/W -15~35°C, step: 1°C
0°C
9.I [5-02] R/W
0: Disabled
1: Enabled
9.I [5-03] R/W -15~35°C, step: 1°C
0°C
9.I [5-04] R/W 0~20°C, step: 1°C
10°C
9.I [5-05] R/W 0~50 A, step: 1 A
50
A
9.I [5-06] R/W 0~50 A, step: 1 A
50
A
9.I [5-07] R/W 0~50 A, step: 1 A
50
A
9.I [5-08] R/W 0~50 A, step: 1 A
50
A
9.I [5-09] R/W 0~20 kW, step: 0,5 kW
20 kW
9.I [5-0A] R/W 0~20 kW, step: 0,5 kW
20 kW
9.I [5-0B] R/W 0~20 kW, step: 0,5 kW
20 kW
9.I [5-0C] R/W 0~20 kW, step: 0,5 kW
20 kW
9.I [5-0D] R/W (*2)
R/O (*1)
(*3)
0: 230V, 1~ (*1) (*2)
1: 230V, 3~ (*2)
2: 400V
,
3~
(
*3
)
9.I [5-0E]
1
9.I [6-00] R/W 2~40°C, step: 1°C
25°C
9.I [6-01] R/W 0~10°C, step: 1°C
2°C
9.I [6-02] R/W 0~10kW, step: 0,2kW
3kW
9.I [6-03] R/W 0~10kW, step: 0,2kW
2kW (*2)
3kW
(
*1
)(
*3
)
9.I [6-04] R/O (*1)
R/W (*2)
(*3)
0~10kW, step: 0,2kW
0kW (*1)
4kW (*2)
6kW
(
*3
)
9.I [6-05]
0
9.I [6-06]
0
9.I [6-07] R/W 0~200W, step: 10W
0W
9.I [6-08] R/W
2~20°C, step: 1°C
10°C
9.I [6-09]
0
9.I [6-0A] R/W 30~[6-0E]°C, step: 1°C
60°C
9.I [6-0B] R/W 30~min(50, [6-0E])°C, step: 1°C
45°C
9.I [6-0C] R/W 30~min(50, [6-0E])°C, step: 1°C
45°C
9.I [6-0D] R/W 0: Reheat only
1: Reheat + sched.
2: Scheduled onl
y
9.I [6-0E] R/W (*4) : 40~75°C, step: 1°C
60°C [E-07]=0
(*4) : 40~80°C, step: 1°C
80°C [E-07]=5
(*5) : 40~60°C, step: 1°C
60
°
C
9.I [7-00] R/W 0~4°C, step: 1°C
0°C
9.I [7-01] R/W 2~40°C, step: 1°C
2°C
--
--
Domestic hot water booster heater hysteresis.
What is the desired comfort storage temperature?
What is the desired eco storage temperature?
What is the desired reheat temperature?
What is the desired DHW production type?
What is the maximum temperature setpoint?
Domestic hot water booster heater overshoot temperature.
What is the equilibrium temperature for the building?
What is the requested limit for DI2?
What is the hysteresis to be used in reheat mode?
--
What is the capacity of the bottom plate heater?
--
--
Backup heater voltage
What is the requested limit for DI2?
What is the requested limit for DI3?
What is the requested limit for DI4?
Automatic cooling/heating changeover hysteresis.
Automatic cooling/heating changeover offset.
Equilibrium: Deactivate backup heater (or external backup heat source in case of a
bivalent system) above the equilibrium temperature for space heating?
Which electric heater has priority?
Which power limitation mode is required on the system?
Which power limitation type is required?
--
Emergency
Operation permission of the booster heater.
Below which outdoor temperature is heating allowed?
Space heating priority.
What is the capacity of the backup heater step 2?
Space heating priority temperature.
Set point correction for domestic hot water temperature.
What is the requested limit for DI1?
Water pipe freeze prevention
--
The temperature difference determining the heat pump ON temperature.
The temperature difference determining the heat pump OFF temperature.
What is the capacity of the booster heater?
What is the capacity of the backup heater step 1?
What is the requested limit for DI3?
What is the requested limit for DI4?
What is the requested limit for DI1?
Backup heater configuration
4P629091-1C - 2022.08
(*1) *3V*_(*2) *6V*_(*3) *9W*_
(*4) EHB*_(*5) EHV*_
(*6) *X*_(*7) *H*