ESIE98–06A Troubleshooting
Part 3 – Troubleshooting 3–25
33
4
5
1
Table 1 with
parameters
The following table shows the settings of the remaining parameters that are not identical for all units:
7
Scroll using
u or d to change the value to 02 for
EUWA5-8-10HB(Z). Scroll using
u or d to change the
value to 03 for EUWY5-8-10HB.
8
Press
s.
You will see parameter H1.
9
Use
u or d
to go to the other parameters.
For the other parameters, refer to the following tables.
Step Action Result
Name Function Parameter
CAREL
(default)
EUWA5-10HB EUWY5-10HB
r3 heating set point direct 40 30
r4 heating hysteresis direct 3 3
rC min. heating set point factory -40 25
rd max.heating set point factory 90 50
F5 min. temp. for cooling speed factory 35 17 0
F6 max. temp. for cooling speed factory 45 19 2
F7 min. temp. for heating speed factory 35 50
F8 max. temp. for heating speed factory 30 48
FA temp. necessary to turn off the
fan (heating mode)
factory 40 40
d1 defrost cycle factory 1 1
d2 time or temp. based defrost factory 0 1
d3 defrost starting temp. factory -5 -10
d4 defrost stopping temp. factory 20 10
d5 min. time interval for defrost
start
factory 10 150
d6 min. duration of defrost cycle factory 0 10
d7 max. duration of defrost cycle factory 5 10
d8 time delay between 2
defrost cycles
factory 30 20
db antifreeze heaters activated
while defrost
factory 0 0
dc delay before defrosting factory 0 0
dd delay after defrosting factory 0 0
A8 set point for the supporting
heater
unit 25 25
A9 heating support-resistance dif-
ferential
unit 3 3
P9 selection of digital input ID2 factory 0 08
H1 unit type factory 2 23