Troubleshooting ESIE98–06A
3–26 Part 3 – Troubleshooting
3
1
3
4
5
Table 2 with
parameters
The following table shows the settings of the remaining parameters that are not identical for all units
referring to the optional items ZL and ZH:
Table 3 with
parameters
The following table shows the settings of the remaining parameters that are identical for all units:
Name Function Parameter
CAREL
(default)
EUWA/Y5-10HB
EUWA5-10HB
(option ZL)
EUWA5-10HB
(option ZH)
rA min. cooling set
point
factory -40 7-7-2
A1 antifreeze-
alarm set point
factory 3 2.5 -11.5 -6.5
A4 antifreeze
heater set point
factory 5 4-10-5
Name Function Parameter
CAREL
(default)
EUWA/Y5-10HB
/3 air coil water probe type factory 1 1
/6 offset for /1 factory 0 0
/7 offset for /2 factory 0 0
/8 offset for /3 factory 0 0
/b digital filter factory 4 4
/c input limitation factory 8 8
/d measurement unit user 0 0
r1 cooling set point direct 12 12
r2 cooling hysteresis direct 3 3
r6 outlet temperature direct - -
r8 air coil temperature direct - -
rb max. cooling set point factory 90 25
c1 min. running time factory 60 0
c2 guard timer factory 6 6
c3 anti recycling timer factory 36 24
c6 time delay at start-up user 0 0
c7 on delay for pump/compressor user 20 15
c8 off delay for pump/compressor user 20 0
c9 running hours of compressor direct 0 -
cb maintenance treshold of c9 unit 0 0
cC running hours of pump direct 0 -
F1 Are there fans? factory 0 1
F2 fans functional logic factory 0 2
F3 min.tension for fan factory 35 0
F4 max. tension for fan control factory 75 100
F9 temp. necessary to turn off the fan (cooling
mode)
factory 20 20
Fb fans starting time factory 4 0