23
Engineering & Physical Data
MODEL
INDOOR FLY35EXV1 FLY40EXV1 FLY40EXV1
OUTDOOR RY35DXV1 RY40DXV1 RY40DXY1
SAFETY
DEVICE
HIGH PRESSURE
SWITCH
TYPE NC
OPEN kPa / psi 2937 / 426
CLOSE kPa / psi 2413 / 350
LOW PRESSURE
SWITCH
TYPE N/A
OPEN kPa / psi N/A
CLOSE kPa / psi N/A
PHASE SEQUENCER N/A YES
DISC. THERMOSTAT SETTING °C / F N/A N/A
MODEL
INDOOR FL50EXV1 FH62CXV1
OUTDOOR R50DXY1 R61DXY1
SAFETY
DEVICE
HIGH PRESSURE
SWITCH
TYPE NC
OPEN kPa / psi 2937 / 426
CLOSE kPa / psi 2413 / 350
LOW PRESSURE
SWITCH
TYPE NC
OPEN kPa / psi 124 / 18
CLOSE kPa / psi 192 / 28
PHASE SEQUENCER YES
DISC. THERMOSTAT SETTING °C / F N/A
MODEL
INDOOR FLY50EXV1 FHY62CXV1
OUTDOOR RY50DXY1 RY61DXY1
SAFETY
DEVICE
HIGH PRESSURE
SWITCH
TYPE NC
OPEN kPa / psi 2937 / 426
CLOSE kPa / psi 2413 / 350
LOW PRESSURE
SWITCH
TYPE N/A
OPEN kPa / psi N/A
CLOSE kPa / psi N/A
PHASE SEQUENCER YES
DISC. THERMOSTAT SETTING °C / F N/A
ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
DAIKIN_FL(Y).indb 23DAIKIN_FL(Y).indb 23 9/27/2012 12:13:20 PM9/27/2012 12:13:20 PM