Indoor Unit: FTXS30/36LVJU SiUS091133
259 Removal Procedure
3
Loosen the screw of the
fan rotor.
4
Remove the fan motor. When reassembling the fan
motor and the fan rotor, provide
as much as 5 mm (0.2 inch) of
play between the side face of
the rotor and the bottom frame.
(1) Insert the fan motor with approx.
5 mm (0.2 inch) left.
(2) Tighten the screw until it stops.
Then give the screw one more
turn.
(3) Rotate the fan rotor and confirm
the fan motor and the fan rotor
are installed appropriately.
(4) Tighten the screw completely if
appropriate.
(5) If not appropriate, go back to
(1).
5
Remove the fan rotor.
Step
Procedure Points
Fan rotor
(R9648)
(R9583)
Fan motor
5 mm (0.2 inch)
Side face of rotor
(R2808)
Side face of
bottom frame
(R9582)
(R9584)