SiUS12-928_A Troubleshooting
Service Diagnosis 126
5.18 Compressor Sensor System Abnormality (24/32 Class)
Remote
Controller
Display
H0
Outdoor Unit LED
Display
A 5 1 4 2 4 3 1 4 1
Method of
Malfunction
Detection
Fault condition is identified by the supply voltage and the DC voltage which is detected before
the compressor startup.
Fault condition is identified by the compressor current which is detected right after the
compressor startup.
If the error repeats 16 times, the system is shut down.
Reset condition: Continuous run for about 5 minutes without any other error
Malfunction
Decision
Conditions
The detected value of the supply voltage and the DC voltage is obviously low or high.
The compressor current does not run when the compressor is started.
Supposed
Causes
Disconnection of reactor
Disconnection of compressor
Defective outdoor unit PCB
Defective compressor