high resoluTion TouCh sCreen DigiTal ThermosTaT
www.DaikinApplied.com 51 IM 1227 • MODELS DC THERMOSTATS
Humidity for TSTATD4272CGT Models Only
Table 20: Humidity Settings Command Levels
●
Humidication Settings
►
●
Humidify setpoint (0%)
►
●
Humidify only with heat – OFF
►
●
Run fan when humidifying – OFF
►
●
Dehumidication Settings
►
●
Dehumidify setpoint (99%)
►
●
Run A/C to dehumidify – OFF
►
●
Maximum Overcool (0°)
►
●
Reheat – OFF
►
Using the Humidity Settings Functions
The Humidity feature allows the thermostat to control a
humidier or use your air conditioner to dehumidify the space.
IMPORTANT
Aux Output Usage must be set for Hum or Dehum for these
settings to take effect. See: AUX Output Settings in the
Installation Settings menu.
●
Humidication Settings
●
Humidify setpoint (0%)
►
Adjust Humidify setpoint. (0% - 60%)
●
Humidify only with heat – OFF
►
When this step is ON, Humidify will only run with a demand
for heat.
●
Run fan when humidifying – OFF
►
When this step is ON, the fan will run with a call for
Humidication.
●
Dehumidication Settings
►
●
Dehumidify setpoint (99%)
►
Adjust Dehumidify setpoint. (25% - 99%)
●
Run A/C to dehumidify – OFF
►
When this step is ON, the A/C system will be used for
Dehumidication.
●
Maximum Overcool (0°)
►
This species how many degrees the A/C system
will run past the cool setpoint to satisfy a demand for
Dehumidication. (0–20 degrees F)
●
Reheat – OFF
►
This turns on electric strip heat during an A/C to dehumidify
demand to help maintain desired room temperature. (Run
A/C to dehumidify must be set to ON and Dip Switch #1 must