EasyManua.ls Logo

Daikin TSTATD4271C - Page 60

Daikin TSTATD4271C
66 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IM 1227 • MODELS DC THERMOSTATS 60 www.DaikinApplied.com
high resoluTion TouCh sCreen DigiTal ThermosTaT
Sample Wiring Diagrams
with Dip Switch Positions
Conventional Heating and Cooling Systems
2 Wire, Heat Only
Residential & Commercial 1 Stage Heating with no Fan.
The thermostat will not work with 2 wires. Either pull new wire or purchase a
model TSTATGAC-2W two-wire kit
GAS/EL
O
GAS
HP
B
ELEC
3 Wire, Heat Only
Residential & Commercial 1 Stage Heating with no Fan.
R – 24VAC Power
C – 24VAC Common
W1/O/B 1st Stage Heat
GAS/EL
O
GAS
HP
B
ELEC
4 Wire, Cool Only
Residential & Commercial 1 Stage Cooling.
R – 24VAC Power
C – 24VAC Common
Y1 1st Stage Cool
G – Fan
GAS/EL
O
GAS
HP
B
ELEC
5 Wire, 1 Stage Cooling, 1 Stage Heat
Residential & Commercial 1 Stage Cooling, with 1 stage Electric Heat.
R – 24VAC Power
C – 24VAC Common
W1/O/B 1st Stage Heat
Y1 1st Stage Cool
G – Fan
GAS/EL
O
GAS
HP
B
ELEC
5 Wire, 1 Stage Cooling, 1 Stage Heat
Residential & Commercial 1 Stage Cooling, with 1 stage Gas Heat.
R – 24VAC Power
C – 24VAC Common
W1/O/B 1st Stage Heat
Y1 1st Stage Cool
GAS/EL
O
GAS
HP
B
ELEC
8 Wire, 2 Stage Cooling, 3 Stage Heat
Residential & Commercial 2 Stage Cooling, with 3 stage Gas Heat.
R – 24VAC Power
C – 24VAC Common
W1/O/B 1st Stage Heat
W2 2nd Stage Heat
W3/AUX 3rd Stage Heat
Y1 1st Stage Cool
Y2 2nd Stage Cool
G – Fan
GAS/EL
O
GAS
HP
B
ELEC
Heat Pump Systems
5 Wire, 1 Stage Cooling, 1 Stage Heat
Residential & Commercial Heat Pump with ‘O’ Reversing Valve
R – 24VAC Power
C – 24VAC Common
W1/O/B – Reversing Valve
Y1 1st Stage Compressor (Cool or Heat)
G – Fan
GAS/EL
O
GAS
HP
B
ELEC
6 Wire, 1 Stage Cooling, 2 Stage Heat
Residential & Commercial Heat Pump with ‘O’ Reversing Valve
R – 24VAC Power
C – 24VAC Common
W1/O/B – Reversing Valve
Y1 1st Stage Compressor (Cool or Heat)
W2 – Aux Heat
GAS/EL
O
GAS
HP
B
ELEC
7 Wire, 2 Stage Cooling, 3 Stage Heat
Residential & Commercial Heat Pump with ‘O’ Reversing Valve.
R – 24VAC Power
C – 24VAC Common
W1/O/B – Reversing Valve
W2 3rd Stage Heat
Y1 1st Stage Compressor (Cool or Heat)
Y2 2nd Stage Compressor (Cool or Heat)
G – Fan
GAS/EL
O
GAS
HP
B
ELEC
(Number of Compressor Stages set to 2)
8 Wire, 2 Stage Cooling, 4 Stage Heat
Residential & Commercial Heat Pump with ‘O’ Reversing Valve.
R – 24VAC Power
C – 24VAC Common
W1/O/B – Reversing Valve
W2 3rd Stage Heat
W3/AUX 4th Stage Heat
Y1 1st Stage Compressor (Cool or Heat)
Y2 2nd Stage Compressor (Cool or Heat)
G – Fan
GAS/EL
O
GAS
HP
B
ELEC
(Number of Compressor Stages set to 2)