FC 300 Instruction Manual
How to Program
" 2-** Brakes
Par.
No. #
Parameter description Default value 4-set-up Change
during
operation
Conver-
sion index
Type
2-0* DC-brake
2-00 DC hold current 50 % All set-ups TRUE 0 Uint8
2-01 DC brake current 50 % All set-ups TRUE 0 Uint16
2-02 DC braking time 10.0 s All se t-ups TRUE -1 Uint16
2-03 DC brake cut-in speed 0 RPM All set-ups TRUE 67 Uint16
2-1* Brake energy funct.
2-10 Brake and over-voltage functions [0] Off All set-ups TRUE - Uint8
2-11 Brake resistor (ohm) Drive dependent All set-ups TRUE 0 Uint16
2-12 Brake powe r limit (kW) Drive dependent All set-ups TRUE 0 Uint32
2-13 Brake power monitoring [0] Off All set-ups TRUE - Uint8
2-15 Brake check [0] Off All set-ups TRUE - Uint8
2-2* Mechanical brake
2-20 Release brake current 0.00 A All set-ups TRUE -2 Uint16
2-21 Activate brake speed [RPM] 0 RPM All set-ups TRUE 6 7 Uint16
2-23 Activate brake delay 0.0 s All set-ups TRUE -1 U int8
*
default setting ()display text []value for use in comm unication via serial comm unication port