FC 300 Instruction Manual
How to Install
" Access to Control Terminals
All terminals to the control cables are located
underneath the terminal cover on the front of the
adjustable frequency drive. Remove the terminal
cover by means of a screwdriver (see illustration).
A1, A 2 and A3 enclosures
A5, B1 and B2 enclosures
"
Electrical Installation, Control Terminals
To mount the cable to the terminal:
1. Strip isolation of 0.34-0.39 in [9-10 mm]
2. Insert a screwdrive
r in the square hole.
3. Insert the cable in the adjacent circular hole.
4. Remove the screwdriver. The cable is now
mounted to the term
inal.
To remove the c able from the terminal:
1. Insert a screwdriver in the square hole.
2. Pull out the cable.
1. 2.
3.
23
MG.33.A6.22 - VLT is a registered Danfoss trademark