FC 300 Instruction Manual
Safety Instructions and General Warning
Equipment containing electrical components may no
tbedisposed
together with domestic waste.
It must be co llected separately as electrical and electronic waste
according to local and currently valid legislatio
n.
Caution
The FC 300 AutomationDrive DC link capacitors remain charged after power has been
disconnected. To avoid an electrical shock hazard, disconnect the FC 300 from the power
supply before carrying ou
tmaintenance. Waitatleastaslongasfollowsbeforeservicingthe
adjustable frequency drive:
FC 300: 0.34 – 10 HP
[0.25–7.5
kW]
4minutes
FC 300: 14.75 – 29.5
HP [11 – 22
kW]
15 minutes
BeawarethattheremaybehighvoltageontheDClinkevenwhentheLEDsareturnedoff.
7
MG.33.A6.22 - VLT is a registered Danfoss trademark