P1K1 P1K5 P2K2 P3K0 P4K0 P5K5 P7K5
Typical Shaft Output [kW] 1.1 1.5 2.2 3 4 5.5 7.5
Enclosure IP20 (only) A3 A3 A3 A3 A3 A3 A3
Output current High overload 160% for 1 min
Continuous (3x525-550 V) [A] 2.1 2.7 3.9 4.9 6.1 9 11
Intermittent (3x525-550 V) [A] 3.4 4.3 6.2 7.8 9.8 14.4 17.6
Continuous kVA (3x551-690 V) [A] 1.6 2.2 3.2 4.5 5.5 7.5 10
Intermittent kVA (3x551-690 V) [A] 2.6 3.5 5.1 7.2 8.8 12 16
Continuous kVA 525 V AC 1.9 2.5 3.5 4.5 5.5 8.2 10
Continuous kVA 690 V AC 1.9 2.6 3.8 5.4 6.6 9 12
Max. input current
Continuous (3x525-550 V) [A] 1.9 2.4 3.5 4.4 5.5 8 10
Intermittent (3x525-550 V) [A] 3.0 3.9 5.6 7.1 8.8 13 16
Continuous kVA (3x551-690 V) [A] 1.4 2.0 2.9 4.0 4.9 6.7 9
Intermittent kVA (3x551-690 V) [A] 2.3 3.2 4.6 6.5 7.9 10.8 14.4
Additional specifications
IP20 max. cable cross section
5)
(mains, motor,
brake and load sharing) [mm
2
(AWG)]
0.2-4 (24-12)
Estimated power loss at rated max. load [W]
4)
44 60 88 120 160 220 300
Weight, enclosure IP20 [kg] 6.6 6.6 6.6 6.6 6.6 6.6 6.6
Efficiency
4)
0.96 0.96 0.96 0.96 0.96 0.96 0.96