1.
2.
3.
4.
5.
-
-
-
Lower cover
DC terminals
Terminal cover
Motor terminals
Ground terminals on drive module
Grounding bar
5.8.4 Connecting the Sine-wave Filter to the Motor
Procedure
Strip a section of the outer cable insulation.
Fasten a connector/cable lug to the end of the stripped cable.
Create an electrical connection between the cable shield and ground by securing the stripped wire under the cable clamp.
Connect the ground cable to the nearest grounding terminal in accordance with the grounding instructions provided in
5.8.6 Connecting to Ground.
Connect the 3-phase AC motor cable to the sine-wave terminals U, V, and W.
If the enclosed drive has 1 sine-wave filter cabinet, run 1 set of motor cables to the cabinet.
If the enclosed drive has 2 sine-wave filter cabinets, run 2 sets of motor cables, 1 set to each sine-wave filter cabinet.
N O T I C E
Each sine-wave cabinet must have the same number of motor phase cables and they must be in quantities of 2
(for example, 2, 4, 6, or 8). 1 cable is not allowed. The cables are required to be equal length.
AQ262141314214en-000301 / 130R0880100 | Danfoss A/S © 2021.11
Electrical Installation
VLT® HVAC Drive FC 102
Operating Guide

Table of Contents

Other manuals for Danfoss Metasys N2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss Metasys N2 and is the answer not in the manual?

Danfoss Metasys N2 Specifications

General IconGeneral
BrandDanfoss
ModelMetasys N2
CategoryDC Drives
LanguageEnglish

Related product manuals