Page #119 background image
8.1.3 Wiring Configuration: Speed
Table 74: Wiring Configuration for Analog Speed Reference (Voltage)
Parameters
+10
V
A IN
A IN
COM
A OUT
COM
XD2.6
XD2.7
XD2.8
XD2.9
XD2.5
XD2.4
A53
U - I
0–10 V
+
-
e30bu073.10
Function
Setting
Parameter 6-10 Terminal 53 Low Voltage
0.07 V*
Parameter 6-11 Terminal 53 High Voltage
10 V*
Parameter 6-14 Terminal 53 Low Ref./Feedb. value
0 Hz
Parameter 6-15 Terminal 53 High Ref./Feedb. Value
50 Hz
*=Default value
Notes/comments:
D IN 37 is an option.
Terminal 53 in the parameter title corresponds to terminal XD2.7 in the control compartment.
Table 75: Wiring Configuration for Analog Speed Reference (Current)
Parameters
+10 V
A IN
A IN
COM
A OUT
COM
+
-
e30bu074.10
A53
U - I
4-20mA
XD2.6
XD2.7
XD2.8
XD2.9
XD2.5
XD2.4
Function
Setting
Parameter 6-12 Terminal 53 Low Current
4 mA*
Parameter 6-13 Terminal 53 High Current
20 mA*
Parameter 6-14 Terminal 53 Low Ref./Feedb. value
0 Hz
Parameter 6-15 Terminal 53 High Ref./Feedb. Value
50 Hz
*=Default value
Notes/comments:
D IN 37 is an option.
Terminal 53 in the parameter title corresponds to terminal XD2.7 in the control compartment.
Table 76: Wiring Configuration for Speed Reference (Using a Manual Potentiometer)
Parameters
+10
V
A IN
A IN
COM
A OUT
COM
A53
U - I
# 5k#
e30bu075.10
XD2.6
XD2.7
XD2.8
XD2.9
XD2.5
XD2.4
Function
Setting
Parameter 6-10 Terminal 53 Low Voltage
0.07 V*
Parameter 6-11 Terminal 53 High Voltage
10 V*
Parameter 6-14 Terminal 53 Low Ref./Feedb. value
0 Hz
Parameter 6-15 Terminal 53 High Ref./Feedb. Value
50 Hz
*=Default value
Notes/comments:
D IN 37 is an option.
Terminal 53 in the parameter title corresponds to terminal XD2.7 in the control compartment.
AQ262141314214en-000301 / 130R0880 | 119Danfoss A/S © 2021.11
Wiring Configuration Examples
VLT® HVAC Drive FC 102
Operating Guide

Table of Contents

Other manuals for Danfoss Metasys N2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss Metasys N2 and is the answer not in the manual?

Danfoss Metasys N2 Specifications

General IconGeneral
BrandDanfoss
ModelMetasys N2
CategoryDC Drives
LanguageEnglish

Related product manuals