- Mains with contactor
[mm
2
(AWG)]
Drive module power loss
at 600 V [W]
(1)(2)(3)
Drive module power loss
at 690 V [W]
(1)(2)(3)
Heat sink overtempera-
ture trip [°C (°F)]
Control card overtem-
perature trip [°C (°F)]
PHF overtemperature
trip [°C (°F)]
Line reactor overtemper-
ature trip [°C (°F)]
dU/dt filter overtemper-
ature trip [°C (°F)]
Sine-wave filter over-
temperature trip [°C (°F)]
1
Typical power loss is at normal conditions and expected to be within ±15% (tolerance relates to variety in voltage and cable conditions.) These
values are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies to dimension-
ing of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control card power
consumptions are included. For power loss data according to EN 50598-2, refer to drives.danfoss.com/knowledge-center/energy-efficiency-direc-
tive/#/. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for slots A and B each
add only 4 W.
2
Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energy efficien-
cy class, see the Ambient Conditions section. For part load losses, see drives.danfoss.com/knowledge-center/energy-efficiency-directive/#/.
3
See also Input Power Option Losses section.
4
If using an output filter, the output frequency is limited further. See the Motor Output (U, V, W) section.
Table 101: Electrical Data, Mains Supply 3x525–690 V AC
Normal overload
110% torque for a duration of 60 s.
Typical shaft output at 550 V [kW]
Typical shaft output at 575 V [hp]
Typical shaft output at 690 V [kW]
AQ262141314214en-000301 / 130R0880158 | Danfoss A/S © 2021.11
Specifications
VLT® HVAC Drive FC 102
Operating Guide