EasyManuals Logo
Home>Danfoss>DC Drives>VLT 3516

Danfoss VLT 3516 User Manual

Danfoss VLT 3516
123 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #63 background imageLoading...
Page #63 background image
VLT
®
Series 3500
61
= ROM default setting. = Normal Danfoss setup. Text in ( ) = display text. Figures in [ ] are used when communicating with the bus.
015 Setup Choice, Programming
(SETUP PROG)
Value:
Pre-programmed (FACTORY SET) [0]
Setup 1 (SETUP 1) [1]
Setup 2 (SETUP 2) [2]
Setup 3 (SETUP 3) [3]
Setup 4 (SETUP 4) [4]
Setup=Parameter 001 (SETUP=P001) [5]
Function:
It is possible to choose the setup that will be affected by pa-
rameter changes. The four menu setups can be pro-
grammed independently of the setup in which the drive is
running (selected in parameter 001). This also determines
the parameter set that is used as the source when copying
setups (parameter 002).
Description of choice:
Pre-programmed
[0] contains the factory-set data and can
be used as a source for data. The language is always En-
glish. It is not possible to change data when running from
this setup.
Setups 1-4
[1]-[4] are four individual setups which can be
used as desired. They can be programmed independently
of the setup currently used.
Setup = Parameter 001
[5] is the pre-selected value nor-
mally used. With this choice, parameter changes will take
effect immediately because they affect the active set.
NOTE:
If the setup being used is changed, the changes
will take effect immediately.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 3516 and is the answer not in the manual?

Danfoss VLT 3516 Specifications

General IconGeneral
BrandDanfoss
ModelVLT 3516
CategoryDC Drives
LanguageEnglish

Related product manuals