VLT
®
Series 3500
94
= ROM default setting. = Normal Danfoss setup. Text in ( ) = display text. Figures in [ ] are used when communicating with the bus.
502 Data Read-Out (DATA READOUT) continued
Description of choice:
Index 0 to 11:
These are the twelve display values which are also avail-
able in the Extended Display. Only the value of the display
is sent via the serial interface, not the unit.
Index “0”. REFERENCE %, represents only external speed
reference signals: analog inputs on terminals 53 and 60,
the pulse from input on terminal 17, and the serial bus ref-
erence. It does not include the jog speed set by parameter
203 or the digital references set by parameters 205 through
208.
Index 12:
A decimal value, which is to be converted to an 8-bit binary
code. This represents the status of the binary inputs.
Example:
Decimal 16
Binary 0 0010000
Terminal 33 32 29 27 19 18 17 16
Index 13 and 14:
A decimal value between 0 and 1023, where 0 corresponds
to 0% and 1023 corresponds to 100% of the selected input
signal, for example 0 to 10 V DC.
Index 15:
A decimal value which is to be converted to a 16-bit binary
number. Each bit represents a warning in accordance with
the table below. When a warning is present, the corre-
sponding bit has the value “1”.
The warnings are described at the end of the programming
section..
Bit Warning
0 Current limit
1 No motor
2 Reference fault
3 Motor overloaded
4 Inverter overloaded
5 Frequency warning, low
6 Frequency warning, high
7 Current warning, low
8 Current warning, high
9 EEPROM fault
10 24 V fault
11 Overcurrent
12 Voltage warning, high
13 Voltage warning, low
14 Overvoltage
15 Undervoltage
Index 16:
A decimal value which is to be converted to a 16-bit binary
number. Each bit represents a control command. When a
control command has been activated, the corresponding bit
has the value “1”.
Index 17:
A decimal value which is to be converted to a 16-bit binary
number. Each bit represents a status message. When a
status message is present, the corresponding bit has the
value “1”.
Index 18:
A decimal value which is to be converted to a 16-bit binary
number. Each bit represents an alarm. When an alarm is
present, the corresponding bit has the value “1”.
Bit Alarm
0 Trip locked
1 Control card or option card fault
2 Current limit
3 Not in use
4 Not in use
5 Auto-optimization
6 Motor overloaded
7 Inverter overloaded
8 Inverter fault
9 Undervoltage
10 Overvoltage
11 Overcurrent
12 Ground fault
13 Fault in DC supply
14 Overtemperature
15 Thermistor input activated,
see parameter 400/terminal 16