4.2.3 Ordering Numbers: Sine Wave Filter Modules, 200–500 V AC
Line power supply 3 x 200–500 V
Adjustable frequency drive size
Minimum switching
frequency
Maximum output
frequency
Part No. IP20 Part No. IP00
Rated filter current at
50 Hz
200–240 V 380–440 V 440–500 V
PK25 PK37 PK37 5 kHz 120 Hz 130B2439 130B2404 2.5 A
PK37 PK55 PK55 5 kHz 120 Hz 130B2439 130B2404 2.5 A
PK75 PK75 5 kHz 120 Hz 130B2439 130B2404 2.5 A
PK55 P1K1 P1K1 5 kHz 120 Hz 130B2441 130B2406 4.5 A
P1K5 P1K5 5 kHz 120 Hz 130B2441 130B2406 4.5 A
PK75 P2K2 P2K2 5 kHz 120 Hz 130B2443 130B2408 8 A
P1K1 P3K0 P3K0 5 kHz 120 Hz 130B2443 130B2408 8 A
P1K5 5 kHz 120 Hz 130B2443 130B2408 8 A
P4K0 P4K0 5 kHz 120 Hz 130B2444 130B2409 10 A
P2K2 P5K5 P5K5 5 kHz 120 Hz 130B2446 130B2411 17 A
P3K0 P7K5 P7K5 5 kHz 120 Hz 130B2446 130B2411 17 A
P4K0 5 kHz 120 Hz 130B2446 130B2411 17 A
P5K5 P11K P11K 4 kHz 60 Hz 130B2447 130B2412 24 A
P7K5 P15K P15K 4 kHz 60 Hz 130B2448 130B2413 38 A
P18K P18K 4 kHz 60 Hz 130B2448 130B2413 38 A
P11K P22K P22K 4 kHz 60 Hz 130B2307 130B2281 48 A
P15K P30K P30K 3 kHz 60 Hz 130B2308 130B2282 62 A
P18K P37K P37K 3 kHz 60 Hz 130B2309 130B2283 75 A
P22K P45K P55K 3 kHz 60 Hz 130B2310 130B2284 115 A
P30K P55K P75K 3 kHz 60 Hz 130B2310 130B2284 115 A
P37K P75K P90K 3 kHz 60 Hz 130B2311 130B2285 180 A
P45K P90K P110 3 kHz 60 Hz 130B2311 130B2285 180 A
P110 P132 3 kHz 60 Hz 130B2312 130B2286 260 A
P132 P160 3 kHz 60 Hz 130B2312 130B2286 260 A
P160 P200 3 kHz 60 Hz 130B2313 130B2287 410 A
P200 P250 3 kHz 60 Hz 130B2313 130B2287 410 A
P250 P315 3 kHz 60 Hz 130B2314 130B2288 480 A
P315 P355 2 kHz 60 Hz 130B2315 130B2289 660 A
P355 P400 2 kHz 60 Hz 130B2315 130B2289 660 A
P400 P450 2 kHz 60 Hz 130B2316 130B2290 750 A
P450 P500 2 kHz 60 Hz 130B2317 130B2291 880 A
P500 P560 2 kHz 60 Hz 130B2317 130B2291 880 A
P560 P630 2 kHz 60 Hz 130B2318 130B2292 1200 A
P630 P710 2 kHz 60 Hz 130B2318 130B2292 1200 A
NOTE!
When using sine-wave filters, the switching frequency should comply with filter specifications in par. 14-01
Switching Frequency
.
4 How to Order VLT
®
AQUA Drive Design Guide
4-12
MG.20.N5.22 - VLT
®
is a registered Danfoss trademark
4

Table of Contents

Other manuals for Danfoss vlt aqua

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt aqua and is the answer not in the manual?

Danfoss vlt aqua Specifications

General IconGeneral
Supply Voltage200-240V, 380-500V, 525-600V
EnclosureIP20
FeaturesEnergy optimization
ApprovalsCE, UL, cUL
Input Voltage Range200-240V, 380-500V, 525-600V
Output Voltage Range0 to supply voltage
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Short circuit, Ground fault
Communication InterfacesPROFIBUS
Cooling MethodAir-cooled