7.4.6 The Data Field
The structure of data blocks depends on the type of message. There are three message types, and the type applies for both control messages (mas-
ter=>slave) and response messages (slave=>master).
The three types of message are:
Process block (PCD):
The PCD is made up of a data block of four bytes (2 words) and contains:
- Control word and reference value (from master to slave)
- Status word and present output frequency (from slave to master).
Parameter block:
The parameter block is used to transfer parameters between master and slave. The data block is made up of 12 bytes (6 words) and also contains the
process block.
Text block:
The text block is used to read or write texts via the data block.
VLT AQUA Low Harmonic Drive Instruction
Manual
7 RS-485 Installation and Set-up
MG.20.T1.22 - VLT
®
is a registered Danfoss trademark
7-7
7

Table of Contents

Other manuals for Danfoss vlt aqua

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt aqua and is the answer not in the manual?

Danfoss vlt aqua Specifications

General IconGeneral
Supply Voltage200-240V, 380-500V, 525-600V
EnclosureIP20
FeaturesEnergy optimization
ApprovalsCE, UL, cUL
Input Voltage Range200-240V, 380-500V, 525-600V
Output Voltage Range0 to supply voltage
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Short circuit, Ground fault
Communication InterfacesPROFIBUS
Cooling MethodAir-cooled

Related product manuals