5-96 Pulse Out #29 Timeout Preset
Range: Function:
0.00 %* [0.00 - 100.00 %] Set the output frequency transferred to the output terminal 29 when the terminal is configured as
'Bus Ctrl Timeout' in par. 5-63
Terminal 29 Pulse Output Variable
[48]. And a time-out is detected.
This parameter only applies for FC 302.
5-97 Pulse Out #X30/6 Bus Control
Range: Function:
0.00 %* [0.00 - 100.00 %] Set the output frequency transferred to the output terminal X30/6 when the terminal is configured
as 'Bus Controlled' in par. 5-66
Terminal X30/6 Pulse Output Variable
, Terminal X30/6 Pulse Output
Variable [45].
5-98 Pulse Out #X30/6 Timeout Preset
Range: Function:
0.00 %* [0.00 - 100.00 %] Set the output frequency transferred to the output terminal X30/6 when the terminal is configured
as 'Bus Ctrl Timeout' in par. 5-66
Terminal X30/6 Pulse Output Variable
[48]. And a time-out is
detected.
FC 300 Programming Guide 3 Parameter descriptions
MG.33.M8.02 - VLT
®
is a registered Danfoss trademark
115