3.12 Parameters: DeviceNet CAN Fieldbus
3.12.1 10-** DeviceNet and CAN Fieldbus
Parameter group for DeviceNet CAN fieldbus parameters.
3.12.2 10-0* Common Settings
Parameter group for configuring common settings for CAN fieldbus options.
10-00 CAN Protocol
Option: Function:
[0] CANopen
[1] * DeviceNet View the active CAN protocol.
NB!
The options depend on installed option.
10-01 Baud Rate Select
Select the fieldbus transmission speed. The selection must correspond to the transmission speed of the master and the other fieldbus nodes.
Option: Function:
[16] 10 Kbps
[17] 20 Kbps
[18] 50 Kbps
[19] 100 Kbps
[20] * 125 Kbps
[21] 250 Kbps
[22] 500 Kbps
10-02 MAC ID
Range: Function:
Application
dependent*
[Application dependant] Selection of station address. Every station connected to the same network must have an unambig-
uous address.
10-05 Readout Transmit Error Counter
Range: Function:
0 N/A* [0 - 255 N/A] View the number of CAN control transmission errors since the last power-up.
10-06 Readout Receive Error Counter
Range: Function:
0 N/A* [0 - 255 N/A] View the number of CAN control receipt errors since the last power-up.
10-07 Readout Bus Off Counter
Range: Function:
0* [0 - 255 ] View the number of Bus Off events since the last power-up.