Select
Initialization
[2] to reset all parameter values to default settings, except for par. 15-03
Power
Up's
, par. 15-04
Over Temp's
, and par. 15-05
Over Volt's
. The frequency converter will reset during
the next power-up.
Par. 14-22
Operation Mode
will also revert to the default setting
Normal operation
[0].
[0] * Normal operation
[1] Control card test
[2] Initialisation
[3] Boot mode
14-24 Trip Delay at Current Limit
Range: Function:
60 s* [0 - 60 s] Enter the current limit trip delay in seconds. When the output current reaches the current limit
(par. 4-18
Current Limit
), a warning is triggered. When the current limit warning has been contin-
uously present for the period specified in this parameter, the frequency converter trips. Disable the
trip delay by setting the parameter to 60 s = OFF. Thermal monitoring of the frequency converter
will still remain active.
14-25 Trip Delay at Torque Limit
Range: Function:
60 s* [0 - 60 s] Enter the torque limit trip delay in seconds. When the output torque reaches the torque limits
(par. 4-16
Torque Limit Motor Mode
and par. 4-17
Torque Limit Generator Mode
), a warning is
triggered. When the torque limit warning has been continuously present for the period specified in
this parameter, the frequency converter trips. Disable the trip delay by setting the parameter to 60
s = OFF. Thermal monitoring of the frequency converter will still remain active.