15-07 Reset Running Hours Counter
Option: Function:
[0] * Do not reset
[1] Reset counter Select
Reset
[1] and press [OK] to reset the Running Hours counter to zero (see par. 15-01
Running
Hours
). This parameter cannot be selected via the serial port, RS 485.
Select
Do not reset
[0] if no reset of the Running Hours counter is desired.
3.16.3 15-1* Data Log Settings
The Data Log enables continuous logging of up to 4 data sources (par. 15-10
Logging Source
) at individual rates (par. 15-11
Logging Interval
). A trigger
event (par. 15-12
Trigger Event
) and window (par. 15-14
Samples Before Trigger
) are used to start and stop the logging conditionally.
15-10 Logging Source
Array [4]
Option: Function:
Select which variables are to be logged.
[0] * None
[1472] VLT Alarm Word
[1473] VLT Warning Word
[1474] VLT Ext. Status Word
[1600] Control Word
[1601] Reference [Unit]
[1602] Reference %
[1603] Status Word
[1610] Power [kW]
[1611] Power [hp]
[1612] Motor Voltage
[1613] Frequency
[1614] Motor Current
[1616] Torque [Nm]
[1617] Speed [RPM]
[1618] Motor Thermal
[1621] Torque [%] High Res.
[1622] Torque [%]
[1625] Torque [Nm] High
[1630] DC Link Voltage
[1632] Brake Energy /s
[1633] Brake Energy /2 min
[1634] Heatsink Temp.
[1635] Inverter Thermal
[1650] External Reference
[1651] Pulse Reference
[1652] Feedback [Unit]
[1660] Digital Input
[1662] Analog Input 53
[1664] Analog Input 54
[1665] Analog Output 42 [mA]
[1666] Digital Output [bin]
3 Parameter descriptions FC 300 Programming Guide