2-25 Brake Release Time
Range: Function:
0.20 s* [0.00 - 5.00 s] This value defines the time it takes for the mechanical brake to open. This parameter must act as
a time-out when brake feedback is activated.
2-26 Torque Ref
Range: Function:
0.00 %* [Application dependant] The value defines the torque applied against the closed mechanical brake, before release
2-27 Torque Ramp Time
Range: Function:
0.2 s* [0.0 - 5.0 s] The value defines the duration of the torque ramp in clockwise direction.
2-28 Gain Boost Factor
Range: Function:
1.00* [1.00 - 4.00 ] Only active in flux closed loop. The function ensures a smooth transition from torque control mode
to speed control mode when the motor takes over the load from the brake.
Illustration 3.4: Brake release sequence for hoist mechanical brake control
I)
Activate brake delay
: The frequency converter starts again from the
mechanical brake engaged
position.
II)
Stop delay
: When the time between successive starts is shorter than the setting in par. 2-24
Stop Delay
, the frequency converter starts
without applying the mechanical brake (e.g. reversing).
3 Parameter descriptions FC 300 Programming Guide
70
MG.33.M8.02 - VLT
®
is a registered Danfoss trademark
3

Other manuals for Danfoss VLT AutomationDrive FC 300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 300 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 300 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 300
CategoryDC Drives
LanguageEnglish

Related product manuals