Application
Settings
I
Load
/I
Motor
> 50
High load at low speed <30% (rated
speed)
Increase parameter 1-17 Voltage filter time const. Increase parameter 1-66 Min. Current
at Low Speed (>100% for longer time can overheat the motor).
If the motor starts oscillating at a certain speed, increase parameter 1-14 Damping Gain. Increase the value in small steps. Depending
on the motor, a good value for this parameter can be 10% or 100% higher than the default value.
Adjust starting torque in parameter 1-66 Min. Current at Low Speed. 100% provides nominal torque as starting torque.
Table 149: Recommendations for Flux Applications
Application
Settings
Low inertia applications
Keep calculated values.
High inertia applications
Parameter 1-66 Min. Current at Low Speed. Increase speed to a value between default and maximum
depending on application. Set ramp times matching the application. Too fast ramp-up causes an
overcurrent/overtorque. Too fast ramp-down causes an overvoltage trip.
High load at low speed
Parameter 1-66 Min. Current at Low Speed. Increase speed to a value between default and maximum
depending on application.
Adjust starting torque in parameter 1-66 Min. Current at Low Speed. 100% provides nominal torque as starting torque.
5.3 Parameter Group 2-** Brakes
5.3.1 2-0* DC Brakes
Parameter group for configuring the DC brake and DC hold functions.
Parameter 2-00 DC Hold Current
Table 150: Parameter 2-00 DC Hold Current
2-00 DC Hold Current
Default value: 50%
Parameter type: Range, 0 - 160%
Setup: All setups
Conversion index: 0
Data type: Uint8
Change during operation: True
N O T I C E
The maximum value depends on the rated motor current. Avoid 100% current for too long. It may damage the motor. In VVC+
control core, low values (<20%) of DC hold may result in wrong currents with larger motor sizes (>90 kW) and should be avoided.
In cases when low DC hold currents with larger motors are required, select Flux control core to ensure the right currents.
Enter a value for holding current as a percentage of the rated motor current I
M,N
set in parameter 1-24 Motor Current. 100% DC hold
current corresponds to I
M,N
. This parameter holds the motor function (holding torque) or preheats the motor. This parameter is ac-
tive if DC hold is selected in parameter 1-72 Start Function [0] or parameter 1-80 Function at Stop [1].
Parameter 2-01 DC Brake Current
Table 151: Parameter 2-01 DC Brake Current
2-01 DC Brake Current
Default value: 50%
Parameter type: Range, 0 - 1000%
Setup: All setups
Conversion index: 0
Data type: Uint16
Change during operation: True
N O T I C E
The maximum value depends on the rated motor current. Avoid 100% current for too long. It may damage the motor.
AU275636650261en-000101 / 130R0334112 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 301

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 301 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 301 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 301
CategoryDC Drives
LanguageEnglish

Related product manuals