Enter the filter time constant. This is a first-order digital low-pass filter time constant for suppressing electrical noise in terminal
X49/5. A high time constant value improves dampening but also increases the time delay through the filter.
5.29.5 36-4* Output X49/7
N O T I C E
The following parameter is only available in FC 302:
Parameter 36-41 Terminal X49/7 Digital Output
Use the parameters in this group to configure the mode of inputs and outputs of VLT® Programmable I/O MCB 115.
Parameter 36-40 Terminal X49/7 Analogue Output
Table 1330: Parameter 36-40 Terminal X49/7 Analogue Output
36-40 Terminal X49/7 Analogue Output
Default value: [0] No operation
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
Select the functionality of terminal X49/7.
Option
Name
Description
[0]*
No operation
Indicates no signal on the analog output.
[52]
MCO
[100]
Output frequency
0 Hz = 0 mA; 100 Hz = 20 mA.
[101]
Reference
Parameter 3-00 Reference Range [Min - Max] 0% = 0 mA; 100% = 20 mA
Parameter 3-00 Reference Range [-Max - Max] -100% = 0 mA; 0% = 10 mA; +100% = 20 mA.
[102]
Feedback
[103]
Motor current
The value is taken from parameter 16-37 Inv. Max. Current. The inverter maximum current (160%
current) is equal to 20 mA.
Example: Inverter normal current (11 kW) is 24 A. 160 %=38.4 A. Motor normal current is 22 A, the
readout is 11.46 mA.
20mA × 22A
38 . 4A
 = 11 . 46mA
When the normal motor current is equal to 20 mA, the output setting of parameter 6-52 Terminal
42 Output Max Scale is:
IVLT, MAX × 100
IMotor, Nom
îš‹ = îš‹
38 . 4 × 100
22
 = 175 %
[104]
Torque rel to limit
The torque setting is related to the setting in parameter 4-16 Torque Limit Motor Mode.
[105]
Torque relate to
rated
The torque is related to the motor torque setting.
[106]
Power
Taken from parameter 1-20 Motor Power [kW].
[107]
Speed
Taken from parameter 3-03 Maximum Reference. 20 mA equals the value in parameter 3-03 Maxi-
mum Reference.
[108]
Torque
Torque reference related to 160% torque.
[109]
Max out freq
0 Hz = 0 mA, parameter 4-19 Max Output Frequency = 20 mA.
AU275636650261en-000101 / 130R0334 | 643Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 301

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 301 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 301 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 301
CategoryDC Drives
LanguageEnglish

Related product manuals