Parameter 2-32 Speed PID Start Integral Time
Table 180: Parameter 2-32 Speed PID Start Integral Time
2-32 Speed PID Start Integral Time
Default value: 20.0 ms
Parameter type: Range, 1.0 - 20000.0 ms
Setup: All setups
Conversion index: -4
Data type: Uint32
Change during operation: True
Enter the speed controller integral time. Obtain quick control through a short integral time, though if the integral time is too short,
the process becomes unstable. An excessively long integral time disables the integral action.
Parameter 2-33 Speed PID Start Lowpass Filter Time
Table 181: Parameter 2-33 Speed PID Start Lowpass Filter Time
2-33 Speed PID Start Lowpass Filter Time
Default value: 2.0 ms
Parameter type: Range, 0.1 - 100.0 ms
Setup: All setups
Conversion index: -4
Data type: Uint16
Change during operation: True
Set a time constant for the speed control low-pass filter. The low-pass filter improves steady-state performance and dampens oscil-
lations on the feedback signal. However, severe filtering can be detrimental to dynamic performance.
Parameter 2-34 Zero Speed Position P Proportional Gain
Table 182: Parameter 2-34 Zero Speed Position P Proportional Gain
2-34 Zero Speed Position P Proportional Gain
Default value: 0.0000
Parameter type: Range, 0.0000 - 1.0000
Setup: All setups
Conversion index: -4
Data type: Uint32
Change during operation: True
N O T I C E
This parameter is only available with software version 48.XX.
Enter the proportional gain for position control at standstill in speed mode.
5.4 Parameter Group 3-** Reference/Ramps
Parameters for handling of reference, definition of limitations, and configuration of the reaction of the drive to changes.
5.4.1 3-0* Reference Limits
Parameter 3-00 Reference Range
Table 183: Parameter 3-00 Reference Range
3-00 Reference Range
Default value: Size related
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
Select the range of the reference signal and the feedback signal. Signal values can be positive only, or positive and negative. The
minimum limit may have a negative value, unless [1] Speed closed loop control or [3] Process is selected in parameter 1-00 Configura-
tion Mode.
AU275636650261en-000101 / 130R0334 | 123Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 301

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 301 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 301 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 301
CategoryDC Drives
LanguageEnglish

Related product manuals