Enter the current (mA) that corresponds to the high reference value set in parameter 35-45 Term. X48/2 High Ref./Feedb. Value.
Parameter 35-44 Term. 48/2 Low Ref./Feedb. Value
Table 1300: Parameter 35-44 Term. 48/2 Low Ref./Feedb. Value
35-44 Term. 48/2 Low Ref./Feedb. Value
Default value: 0 ReferenceFeedbackUnit
Parameter type: Range, -999999.999 - 999999.999
ReferenceFeedbackUnit
Setup: All setups
Conversion index: 0
Data type: Int32
Change during operation: True
Enter the reference or feedback value (in RPM, Hz, bar, and so on) that corresponds to the voltage or current set in parameter 35-42
Term. X48/2 Low Current.
Parameter 35-45 Term. 48/2 High Ref./Feedb. Value
Table 1301: Parameter 35-45 Term. 48/2 High Ref./Feedb. Value
35-45 Term. 48/2 High Ref./Feedb. Value
Default value: 100 ReferenceFeedbackU-
nit
Parameter type: Range, -999999.999 - 999999.999
ReferenceFeedbackUnit
Setup: All setups
Conversion index: 0
Data type: Int32
Change during operation: True
Enter the reference or feedback value (in RPM, Hz, bar, and so on) that corresponds to the voltage or current set in parameter 35-43
Term. X48/2 High Current.
Parameter 35-46 Term. X48/2 Filter Time Constant
Table 1302: Parameter 35-46 Term. X48/2 Filter Time Constant
35-46 Term. X48/2 Filter Time Constant
Default value: 0.001 s
Parameter type: Range, 0.001 - 10 s
Setup: All setups
Conversion index: 0
Data type: Uint16
Change during operation: True
Enter the filter time constant. This is a first-order digital low-pass filter time constant for suppressing electrical noise in terminal
X48/2. A high time constant value improves dampening but also increases the time delay through the filter.
5.29 Parameter Group 36-** Programmable I/O Option
Parameters for configuring VLT® Programmable I/O MCB 115.
Parameters in this group are only active if VLT® Programmable I/O MCB 115 is installed.
5.29.1 36-0* I/O Mode
N O T I C E
The following parameters are only available in FC 302:
Parameter 36-00 Terminal X49/1 Mode
Parameter 36-01 Terminal X49/3 Mode
Parameter 36-02 Terminal X49/5 Mode
Parameter 36-00 Term. X49/1 Mode
Table 1303: Parameter 36-00 Term. X49/1 Mode
36-00 Term. X49/1 Mode
Default value: [1] Voltage
Parameter type: Option
Setup: All setups
Conversion index: -
Data type: Uint8
Change during operation: True
AU275636650261en-000101 / 130R0334636 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 301

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 301 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 301 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 301
CategoryDC Drives
LanguageEnglish

Related product manuals