Guarantees a minimum off-time for the capacitors. The timer starts once the AHF capacitor disconnects and has to expire before the
output is allowed to be on again. It only turns on again if the drive power is 20–30%.
5.6.9 5-9* Bus-controlled
N O T I C E
The following parameters are only available in FC 302:
Parameter 5-95 Pulse Out #29 Bus Control
Parameter 5-96 Pulse Out #29 Timeout Preset
This parameter group selects digital and relay outputs via a fieldbus setting.
Parameter 5-90 Digital & Relay Bus Control
Table 389: Parameter 5-90 Digital & Relay Bus Control
5-90 Digital & Relay Bus Control
Parameter type: Range, 0 - 0xFFFFFFFF
Change during operation: True
This parameter holds the state of the digital outputs and relays that is controlled by bus. A logical 1 indicates that the output is high
or active. A logical 0 indicates that the output is low or inactive.
Table 390: Bus-controlled Digital Outputs and Relays
Digital output terminal 27
Digital output terminal 29
Digital output terminal X30/6
Digital output terminal X30/7
Option B relay 1 output terminal
Option B relay 2 output terminal
Option B relay 3 output terminal
Reserved for future terminals
Option C relay 1 output terminal
Option C relay 2 output terminal
Option C relay 3 output terminal
Option C relay 4 output terminal
Option C realy 5 output terminal
Option C relay 6 output terminal
AU275636650261en-000101 / 130R0334 | 229Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide