Parameter 8-53 Start Select
Table 530: Parameter 8-53 Start Select
8-53 Start Select
Default value: [3] Logic OR
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
Select the trigger for the start function.
Option
Name
Description
[0]
Digital input
A digital input triggers the start function.
[1]
Bus
A serial communication port or the fieldbus triggers the start function.
[2]
Logic AND
The fieldbus/serial communication port and a digital input trigger the start function.
[3]*
Logic OR
The fieldbus/serial communication port or a digital input triggers the start function.
Parameter 8-54 Reversing Select
Table 531: Parameter 8-54 Reversing Select
8-54 Reversing Select
Default value: Size related
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
Select the trigger for the reversing function.
Option
Name
Description
[0]
Digital input
A digital input triggers the reversing function.
[1]
Bus
A serial communication port or the fieldbus triggers the reversing function.
[2]
Logic AND
The fieldbus/serial communication port and a digital input trigger the reversing function.
[3]
Logic OR
The fieldbus/serial communication port or a digital input triggers the reversing function.
Parameter 8-55 Set-up Select
Table 532: Parameter 8-55 Set-up Select
8-55 Set-up Select
Default value: [3] Logic OR
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
Select the trigger for the setup selection.
Option
Name
Description
[0]
Digital input
A digital input triggers the setup selection.
[1]
Bus
A serial communication port or the fieldbus triggers the setup selection.
[2]
Logic AND
The fieldbus/serial communication port and a digital input trigger the setup selection.
[3]*
Logic OR
The fieldbus/serial communication port or a digital input triggers the setup selection.
AU275636650261en-000101 / 130R0334300 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide