Option
Name
Description
[230]
Comparator 8
[231]
Comparator 9
[232]
Logic rule 6
[233]
Logic rule 7
[234]
Logic rule 8
[235]
Logic rule 9
[236]
SL time-out 8
[237]
SL time-out 9
[238]
RS flipflop 8
[239]
RS flipflop 9
Parameter 13-91 Alert Action
Table 696: Parameter 13-91 Alert Action
13-91 Alert Action
Default value: [0] Info
Parameter type: Option, Array [10]
Setup: 2 setups
Conversion index: -
Data type: Uint8
Change during operation: True
N O T I C E
For safety reasons, this parameter cannot be changed when there is an active alarm.
Select the action that the drive performs when the event defined in parameter 13-90 Alert Trigger occurs.
Option
Name
Description
[0]*
Info
[1]
Warning
[2]
Freeze output
[3]
Freeze output & warn
[4]
Stop
[5]
Stop & warning
[6]
Jogging
[7]
Jogging & warning
[8]
Max speed
[9]
Max speed & warn
[10]
Stop and trip
[11]
Stop and w manual reset
AU275636650261en-000101 / 130R0334 | 449Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide