Parameter 14-42 Minimum AEO Frequency
Table 734: Parameter 14-42 Minimum AEO Frequency
14-42 Minimum AEO Frequency
Default value: Size related
Parameter type: Range, 0 - 255 Hz
Setup: All setups
Conversion index: 0
Data type: Uint8
Change during operation: True
N O T I C E
This parameter is not active when parameter 1-10 Motor Construction is set to [1] PM non-salient SPM.
Enter the minimum frequencyat which the automatic energy optimization (AEO)is to be active.
Parameter 14-43 Motor Cosphi
Table 735: Parameter 14-43 Motor Cosphi
14-43 Motor Cosphi
Default value: Size related
Parameter type: Range, 0.40 - 0.95
Setup: All setups
Conversion index: -2
Data type: Uint16
Change during operation: True
The Cos(phi) setpoint is automatically set for optimum AEO performance. This parameter should normally not be altered. However,
in some situations it may be necessary to enter a new value to fine-tune.
Parameter 14-44 d-axis Reference Gain
Table 736: Parameter 14-44 d-axis Reference Gain
14-44 d-axis Reference Gain
Default value: 100%
Parameter type: Range, 0 - 200%
Setup: All setups
Conversion index: 0
Data type: Uint8
Change during operation: True
Adjustment parameter for the d-axis current. 100% indicates maximum torque per ampere value based on motor parameters. In-
creasing the maximum torque can improve the power factor of the machine, which may increase the current consumption. The
adjustment parameter allows to:
Adjust minimum current consumption, allowing for tolerances in the motor parameters.
Obtain the optimal balance between current consumption and power factor of the machine at a given point of operation.
Parameter 14-46 PROFIEnergy Times
Table 737: Parameter 14-46 PROFIEnergy Times
14-46 PROFIEnergy Times
Default value: Size related
Parameter type: Range, 0 - 0x7ffffff, Array [3]
Setup: All setups
Conversion index: 0
Data type: Uint32
Change during operation: True
Parameter with an array of 3. [0] Time to pause, [1] Time min stay, [2] Time regular operate.
Parameter 14-47 PROFIEnergy State
Table 738: Parameter 14-47 PROFIEnergy State
14-47 PROFIEnergy State
Default value: [255] Ready to operate
Parameter type: Option
Setup: 2 setups
Conversion index: -
Data type: Uint8
Change during operation: False
AU275636650261en-000101 / 130R0334466 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 301

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 301 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 301 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 301
CategoryDC Drives
LanguageEnglish

Related product manuals