20mA × 22A
38 . 4A
 = 11 . 46mA
When the normal motor current is equal to 20 mA, the output setting of parameter 6-52 Terminal
42 Output Max Scale is:
IVLT, MAX × 100
IMotor, Nom
îš‹ = îš‹
38 . 4 × 100
22
 = 175 %
The torque setting is related to the setting in parameter 4-16 Torque Limit Motor Mode.
The torque is related to the motor torque setting.
Taken from parameter 1-20 Motor Power [kW].
Taken from parameter 3-03 Maximum Reference. 20 mA equals the value in parameter 3-03 Maxi-
mum Reference.
Torque reference related to 160% torque.
0 Hz = 0 mA, parameter 4-19 Max Output Frequency = 20 mA.
The torque setting is related to the motor torque setting.
An output value set from fieldbus process data. The output works independently of internal func-
tions in the drive.
Parameter 4-54 Warning Reference Low defines the behavior of the analog output in case of field-
bus timeout.
Parameter 36-51 Terminal X49/9 Digital Output
Table 1337: Parameter 36-51 Terminal X49/9 Digital Output
36-51 Terminal X49/9 Digital Output
Default value: [0] No operation
Change during operation: True