EasyManuals Logo

Danfoss VLT AutomationDrive FC 360 User Manual

Danfoss VLT AutomationDrive FC 360
78 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #54 background imageLoading...
Page #54 background image
Symptom Possible cause Test Solution
Motor is not
reaching maximum
speed
Frequency limits are set incorrectly
Check output limits in
parameter 4-14 Motor Speed High Limit
[Hz] and parameter 4-19 Max Output
Frequency.
Program correct limits.
Reference input signal not scaled
correctly
Check reference input signal scaling in
parameter group 6-** Analog I/O mode
and parameter group 3-1* References.
Program correct settings.
Motor speed is
unstable
Possible incorrect parameter settings
Check the settings of all motor
parameters, including all motor
compensation settings. For closed-
loop operation, check PID settings.
Check settings in parameter group 6-
** Analog I/O mode.
Motor runs roughly Possible overmagnetization
Check for incorrect motor settings in
all motor parameters.
Check motor settings in parameter
groups 1-2* Motor data, 1-3* Adv
motor data, and 1-5* Load indep.
setting.
Motor does not
brake
Possible incorrect settings in the
brake parameters. Possible too short
ramp-down times.
Check brake parameters. Check ramp
time settings.
Check parameter groups 2-0* DC brake
and 3-0* Reference limits.
Open power fuses
or circuit breaker
trip
Phase-to-phase short
Motor or panel has a short phase-to-
phase. Check motor and panel phase
for shorts.
Eliminate any shorts detected.
Motor overload
Motor is overloaded for the
application.
Perform the start-up test and verify
that motor current is within speci-
cations. If motor current is exceeding
nameplate full load current, the
motor may run only with reduced
load. Review the specications for the
application.
Loose connections
Perform pre-start-up check for loose
connections.
Tighten loose connections.
Mains current
imbalance greater
than 3%
Problem with mains power (see
alarm 4, Mains phase loss
description)
Rotate input power leads into the
frequency converter 1 position: A to B,
B to C, C to A.
If the imbalanced leg follows the
wire, it is a power problem. Check
mains supply.
Problem with the frequency
converter unit
Rotate input power leads into the
frequency converter 1 position: A to B,
B to C, C to A.
If the imbalanced leg stays on same
input terminal, it is a problem with
the unit. Contact the supplier.
Motor current
imbalance greater
than 3%
Problem with motor or motor wiring
Rotate output motor leads 1 position:
U to V, V to W, W to U.
If the imbalanced leg follows the
wire, the problem is in the motor or
motor wiring. Check motor and
motor wiring.
Problem with the frequency
converter unit
Rotate output motor leads 1 position:
U to V, V to W, W to U.
If the imbalanced leg stays on same
output terminal, it is a problem with
the unit. Contact the supplier.
Acoustic noise or
vibration (for
example a fan blade
is making noise or
vibrations at certain
frequencies)
Resonances, for example, in the
motor/fan system
Bypass critical frequencies by using
parameters in parameter group 4-6*
Speed Bypass.
Check if noise and/or vibration have
been reduced to an acceptable limit.
Turn o overmodulation in
parameter 14-03 Overmodulation.
Increase resonance damping in
parameter 1-64 Resonance Dampening.
Table 7.4 Troubleshooting
Diagnostics and Troubleshoo...
VLT
®
AutomationDrive FC 360
52 Danfoss A/S © 03/2017 All rights reserved. MG06A702
77

Other manuals for Danfoss VLT AutomationDrive FC 360

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 360 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 360 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 360
CategoryDC Drives
LanguageEnglish

Related product manuals