16-11 Power [HP]
Range: Function:
0 HP
*
[0 to 1000 HP]
View the motor power in HP. The value shown is calculated on the basis of the actual motor voltage and motor
current. The value is filtered, and therefore approximately 30 ms may pass from when an input value changes
to when the data read-out values change.
16-12 Motor Voltage
Range: Function:
0.0V
*
[0.0 - 6000.0 V]
View the motor voltage, a calculated value used for controlling the motor.
16-13 Motor Frequency
Range: Function:
0.0Hz
*
[0.0 - 6500.0 Hz]
View the motor frequency, without resonance dampening.
16-14 Motor Current
Range: Function:
0 A
*
[0 to 1856 A]
View the motor current measured as a mean value, IRMS. The value is filtered, and thus approximately 30 ms
may pass from when an input value changes to when the data read-out values change.
16-15 Frequency [%]
Range: Function:
0.00%
*
[-100.00 - 100.00 %]
View a two-byte word reporting the actual motor frequency (without resonance dampening) as a percentage
(scale 0000-4000 Hex) of par. 4-19
Max. Output Frequency
. Set par. 9-16 index 1 to send it with the Status Word
instead of the MAV.
16-16 Torque [Nm]
Range: Function:
0.0Nm
*
[-3000.0 - 3000.0 Nm]
View the torque value with sign, applied to the motor shaft. Linearity is not exact between 110% motor current
and torque in relation to the rated torque. Some motors supply more than 160% torque. Consequently, the min.
value and the max. value will depend on the max. motor current as well as the motor used. The value is filtered,
and thus approx. 1.3 seconds may pass from when an input changes value to when the data read-out values
change.
16-17 Speed [RPM]
Range: Function:
0 RPM
*
[-30000 - 30000 RPM]
View the actual motor RPM.
16-18 Motor Thermal
Range: Function:
0 %
*
[0 - 100 %]
View the calculated thermal load on the motor. The cut-out limit is 100%. The basis for calculation is the ETR
function selected in par.1-90.
16-22 Torque
Range: Function:
[-200% - 200%] This is a read out parameter only.
Shows the actual torque yielded in percentage of the rated torque, based on the setting of the motor size and
rated speed in
Motor Power [kW]
, par. 1-20 or
Motor Power [Hp]
, par. 1-21 and
Motor Nominal Speed
, par. 1-25.
This is the value monitored by the
Broken Belt Function
set in par. 22-6*.
3.16.4. 16-3* Drive Status
Parameters for reporting the status of the frequency converter.
3. Parameter Description VLT
®
HVAC Drive Programming Guide
142
MG.11.C5.02 - VLT
®
is a registered Danfoss trademark
3

Other manuals for Danfoss VLT FC 100 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 100 Series and is the answer not in the manual?

Danfoss VLT FC 100 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 100 Series
CategoryDC Drives
LanguageEnglish

Related product manuals