Date format will depend on setting in par. 0-71,
Date Format
, and time format on setting in par. 0-72,
Time
Format
.
NB!
The frequency converter has no back up of the clock function and the set date/time will reset to default (2000-01-01 00:00) after a
power down unless a Real Time Clock module with back up is installed. Consequently the logging will be stopped until date/time is
readjusted in par. 0-70,
Set Date and Time
. In par. 0-79,
Clock Fault
, it is possible to program for a Warning in case clock not has been
set properly, e.g. after a power down.
NB!
When mounting an Analog I/O MCB109 option card, a battery back up of the date and time is included.
23-64 Timed Period Stop
Range: Function:
2000-01-01 00:00
*
[2000-01-01
00:00 - 2099-12-31 23:59]
Set the date and time at which the Trend Analyses must stop update of the Timed Bin counters.
Date format will depend on setting in par. 0-71,
Date Format
, and time format on setting in par. 0-72,
Time
Format
.
NB!
When mounting an Analog I/O MCB109 option card, a battery back up of the date and time is included.
23-65 Minimum Bin Value
Range: Function:
[0 - 100%] Array with 10 elements ([0]-[9] below parameter number in display). Press OK and step between elements by
means of
and
buttons on the LCP.
Set the minimum limit for each interval in par. 23-61,
Continuous Bin Data
, and par. 23-62,
Timed Bin Data
.
Example: if selecting
counter
[1] and changing setting from 10% to 12%,
counter
[0] will be based on the interval
0 - <12% and
counter
[1] on interval 12% - <20%.
23-66 Reset Continuous Bin Data
Option: Function:
Select
Do reset
[1] to reset all values in par. 23-61,
Continuous Bin Data
.
After pressing OK the setting of the parameter value will automatically change to
Do not reset
[0].
[0]
*
Do not reset
[1] Do reset
23-67 Reset Timed Bin Data
Option: Function:
Select
Do reset
[1] to reset all counters in par. 23-62,
Timed Bin Data
.
After pressing OK the setting of the parameter value will automatically change to
Do not reset
[0].
[0]
*
Do not reset
[1] Do reset
VLT
®
HVAC Drive Programming Guide 3. Parameter Description
MG.11.C5.02 - VLT
®
is a registered Danfoss trademark
199
3

Other manuals for Danfoss VLT FC 100 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 100 Series and is the answer not in the manual?

Danfoss VLT FC 100 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 100 Series
CategoryDC Drives
LanguageEnglish

Related product manuals