25-44 Staging Speed [RPM]
Option: Function:
0 N/A Readout of the below calculated value for Staging Speed When adding a fixed speed pump, in order to prevent
an overshoot of pressure, the variable speed pump ramps down to a lower speed. When the variable speed
pump reaches the “Staging Speed” the fixed speed pump is staged on. Staging Speed calculation is based on
Staging Threshold
, par. 25-42, and
Motor Speed High Limit [RPM]
, par. 4-13.
Staging Speed is calculated with the following formula:
η
STAGE
= η
HIGH
η
STAGE
%
100
where n
HIGH
is Motor Speed High Limit and n
STAGE100%
is the value of Staging Threshold.
25-45 Staging Speed [Hz]
Option: Function:
0 N/A Readout of the below calculated value for Staging Speed When adding a fixed speed pump, in order to prevent
an overshoot of pressure, the variable speed pump ramps down to a lower speed. When the variable speed
pump reaches the “Staging Speed” the fixed speed pump is staged on. Staging Speed calculation is based on
Staging Threshold
, par. 25-42, and
Motor Speed High Limit [Hz]
, par. 4-14.
Staging Speed is calculated with the following formula:
η
STAGE
= η
HIGH
η
STAGE
%
100
where n
HIGH
is Motor Speed High Limit and n
STAGE100%
is the value of
Staging Threshold.
25-46 Destaging Speed [RPM]
Option: Function:
0 N/A Readout of the below calculated value for Destaging Speed. When removing a fixed speed pump, in order to
prevent an undershoot of pressure, the variable speed pump ramps up to a higher speed. When the variable
speed pump reaches the “Destaging Speed” the fixed speed pump is destaged. Destaging Speed is calculated
based on
Destaging Threshold
, par. 25-43, and
Motor Speed High Limit
, par. 4-13.
Destaging Speed is calculated with the following formula:
η
DESTAGE
= η
HIGH
η
DESTAGE
%
100
where n
HIGH
is Motor Speed High Limit and n
DESTAGE100%
is the
value of Destaging Threshold.
25-47 Destaging Speed [Hz]
Option: Function:
Readout of the below calculated value for Destaging Speed. When removing a fixed speed pump, in order to
prevent an undershoot of pressure, the variable speed pump ramps up to a higher speed. When the variable
speed pump reaches the “Destaging Speed” the fixed speed pump is destaged. Destaging Speed is calculated
based on
Destaging Threshold
, par. 25-43, and
Motor Speed High Limit [Hz]
, par. 4-14.
Destaging Speed is calculated with the following formula:
η
DESTAGE
= η
HIGH
η
DESTAGE
%
100
where n
HIGH
is Motor Speed High Limit and n
DESTAGE100%
is the value of Destaging Threshold.
3. Parameter Description VLT
®
HVAC Drive Programming Guide
216
MG.11.C5.02 - VLT
®
is a registered Danfoss trademark
3

Other manuals for Danfoss VLT FC 100 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 100 Series and is the answer not in the manual?

Danfoss VLT FC 100 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 100 Series
CategoryDC Drives
LanguageEnglish

Related product manuals