3.23.5. 25-5* Alternation Settings
Parameters for defining the conditions for alternation of the variable speed pump (lead), if selected as part of the control strategy.
25-50 Lead Pump Alternation
Option: Function:
Lead pump alternation equalizes the use of pumps by periodically changing the pump that is speed controlled.
This ensures that pumps are equally used over time. Alternation equalizes the usage of pumps by always choos-
ing the pump with the lowest number of used hours to stage on next.
[0]
*
Off No alternation of lead pump function will take place. It is not possible to set this parameter to options other that
Off
[0] if
par. 25-03, Motor Start
, is set other than
Direct on Line
[0].
[1] At Staging Alternation of the lead pump function will take place when staging another pump.
[2] At Command Alternation of the lead pump function will take place at an external command signal or a pre-programmed event.
See
par. 25-51, Alternation Event
, for available options.
[3] At Staging or at Com-
mand
Alternation of the variable speed (lead) pump will take place at staging or the “At Command” signal. (See above.)
NB!
It is not possible to select other than
Off
[0] if
par. 25-05, Fixed Lead Pump
, is set to
Yes
[1].
VLT
®
HVAC Drive Programming Guide 3. Parameter Description
MG.11.C5.02 - VLT
®
is a registered Danfoss trademark
217
3

Other manuals for Danfoss VLT FC 100 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 100 Series and is the answer not in the manual?

Danfoss VLT FC 100 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 100 Series
CategoryDC Drives
LanguageEnglish

Related product manuals