2.1.14. Initialisation to Default Settings
Initialise the frequency converter to default settings in two ways:
Recommended initialisation (via par. 14-22)
1. Select par. 14-22
2. Press [OK]
3. Select “Initialisation
4. Press [OK]
5. Cut off the mains supply and wait until the display turns off.
6. Reconnect the mains supply - the frequency converter is now
reset.
7. Change par. 14-22 back to
Normal Operation
.
NB!
Resets parameters selected in Personal Menu with default factory setting.
Par. 14-22 initialises all except:
14-50
RFI 1
8-30
Protocol
8-31
Address
8-32
Baud Rate
8-35
Minimum Response Delay
8-36
Max Response Delay
8-37
Max Inter-char Delay
15-00 to 15-05 Operating data
15-20 to 15-22 Historic log
15-30 to 15-32 Fault log
Manual initialisation
1. Disconnect from mains and wait until the display turns off.
2a. Press [Status] - [Main Menu] - [OK] at the same time while power up for LCP 102, Graphical Display
2b. Press [Menu] while power up for LCP 101, Numerical Display
3. Release the keys after 5 s.
4. The frequency converter is now programmed according to default settings.
This procedure initializes all except: 15-00,
Operating Hours
; 15-03,
Power-up's
; 15-04,
Over temp's
; 15-05,
Over volt's
.
NB!
When you carry out manual initialisation, you also reset serial communication, RFI filter settings (par. 14-50) and fault log settings.
Removes parameters selected in
Personal Menu
.
NB!
After initialization and power cycling, the display will not show any information until after a couple of minutes.
2. How to Programme VLT
®
HVAC Drive Programming Guide
22
MG.11.C5.02 - VLT
®
is a registered Danfoss trademark
2

Other manuals for Danfoss VLT FC 100 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 100 Series and is the answer not in the manual?

Danfoss VLT FC 100 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 100 Series
CategoryDC Drives
LanguageEnglish

Related product manuals